Please do not use the Network Cable as the Cable for the Electric Lock to the Controller!
2016-11-08 16:52
Details of the problem:

Can the cable of the electric lock be replaced by a network cable?

Expert answer:

The line from the electric lock to the access control board in the access control construction looks very ordinary, but the irregular use of the line can easily cause the failure phenomenon that is difficult to find the cause, this must be paid attention to!

Due to the relatively large working current of various electric locks (compared to other devices in the access control system, such as access control board and access card readers), the electric locks are at a certain distance from the controller, and the voltage drop on the lock wires will be relatively large. If the pressure drop is too large, the electric lock will sometimes be able to move, sometimes not (such as the magnetic lock sometimes has insufficient suction). Shows that the door switch is abnormal. It may even grab current resources with the controller, making the controller insufficient power supply, restarting or even crashing.

Some engineers are convenient for wiring or purchasing, using network cables to wire the electric lock to the controller can easily cause malfunctions, although there seems to be no problem during debugging, problems will often occur after a period of time.

If the cable length from the electric lock to the controller is less than 50 meters, a two-core power cord with a cross-sectional area of 1.0 square millimeter is required, and no shielding is required, if it exceeds 50 meters, please double and add a two-core power cord for parallel power supply. If the cable length is greater than 100 meters, it is recommended to move the controller closer to the door electric lock to shorten the wiring distance. The cross-sectional area of the network cable is 0.2 square millimeters, which is 5 times smaller than our standard wire, so it is absolutely impossible, even if the distance between the controller and the electric lock is very short. The electric lock door magnetic signal line can be a network cable. Some people combine the four strands of the network cable to power the electric lock, although it is close to the norm in theory, it is not recommended. Doing so will cause other hidden dangers such as unstable connection terminals.

Stephanie Stephanie Stephanie Ellie Ellie Ellie Victoria Victoria Victoria Olivia Olivia Olivia Isabella Isabella Isabella Jayden Jayden Jayden Lucas Lucas Lucas Dylan Dylan Dylan Ryan Ryan Ryan Noah Noah Noah

Sweep the concern Yingze electronic official WeChat

x
Sample Apply
※ Please fill in your information, our company will deal with your problem as soon as possible.
主站蜘蛛池模板: 美女黄污网站| 欧美性性性性性色大片免费的| 国产成人高清| 欧美日韩国产在线人成| 18岁黄色| 大学生毛片a左线播放| 亚洲一区二区三区视频| 免费特级片| 国产三级不卡| 国产精品综合一区二区三区| 成人精品网| 国产日韩欧美二区| 免费无遮挡十八女禁污污网站| 亚洲色图另类图片| 一级毛片a免费播放王色| 日韩专区一区| 亚洲国产精品va在线观看麻豆| 欧美aaa毛片免费看| 国产中文字幕亚洲| 草草网| 综合欧美视频一区二区三区| 国产成人麻豆tv在线观看| 九九热这里只有国产精品| 起视碰碰97摸摸碰碰视频 | 婷婷六月丁香色婷婷网| 91精品免费观看| 一级特黄国产高清毛片97看片| 日韩一区二区在线视频| 古代级a毛片在线| 在线观看一区二区精品视频| 免费a级毛片在线观看| 欧美成人xxxxxxxx在线| 国产区1| 国产亚洲一区二区三区不卡| 国产黄色电影| 国产精品久久99| 狠狠色丁香婷婷综合| 亚洲三级毛片| 1313午夜精品久久午夜片| yiren22亚洲综合高清一区| 一级黄色免费|